Backflow assembly test · 5568 Hickory Ln
ApprovedFiled Feb 11, 2026 by Logan Whitcomb, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Feb 11, 2026
- Assembly type
- DC
- Serial number
- Z991327
- Size
- 1
- Test gauge serial
- G-5383
- Gauge calibration date
- May 25, 2025
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-70-01294
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.