← Backflow review queue
Backflow assembly test · Station Self Storage
ApprovedFiled Oct 21, 2024 by Taylor Pruitt, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 21, 2024
- Assembly type
- RP
- Serial number
- W172333
- Size
- 4
- Test gauge serial
- G-5624
- Gauge calibration date
- Jul 28, 2024
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-20-01009
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3652 Turkey Hill Way
Owner: Marsh Holdings LLC
Parcel 069-20-01009