Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Self Storage

Approved

Filed Oct 21, 2024 by Taylor Pruitt, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Oct 21, 2024
Assembly type
RP
Serial number
W172333
Size
4
Test gauge serial
G-5624
Gauge calibration date
Jul 28, 2024
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-20-01009
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3652 Turkey Hill Way
Owner: Marsh Holdings LLC
Parcel 069-20-01009