← Backflow review queue
Backflow assembly test · 6850 Pine Knoll Dr
ApprovedFiled Jul 19, 2025 by Logan Whitcomb, Ridge Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jul 19, 2025
- Assembly type
- RP
- Serial number
- W372164
- Size
- 3/4
- Test gauge serial
- G-3634
- Gauge calibration date
- Oct 12, 2024
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-44-01158
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.