Backflow assembly test · 334 Sycamore Way

Approved

Filed Mar 19, 2025 by Blake Marsh, Heritage Backflow Testing · filed from phone

Report

Date of service
Mar 19, 2025
Assembly type
PVB
Serial number
K132887
Size
1
Test gauge serial
G-2203
Gauge calibration date
Oct 20, 2024
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-34-01160
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

334 Sycamore Way
Owner: Jordan Whitcomb
Parcel 069-34-01160