Backflow assembly test · Riverside Grill
ApprovedFiled May 21, 2026 by Blake Marsh, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 21, 2026
- Assembly type
- RP
- Serial number
- W538974
- Size
- 1
- Test gauge serial
- G-1192
- Gauge calibration date
- Apr 2, 2026
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 1.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-18-01118
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7411 Old Church Rd
Owner: Harlow Holdings LLC
Parcel 069-18-01118