Backflow assembly test · Riverside Grill
ApprovedFiled Jun 1, 2024 by Hayden Ramirez, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Jun 1, 2024
- Assembly type
- RP
- Serial number
- W538974
- Size
- 1
- Test gauge serial
- G-8949
- Gauge calibration date
- Oct 24, 2023
- Check valve 1
- 8.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-18-01118
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7411 Old Church Rd
Owner: Harlow Holdings LLC
Parcel 069-18-01118