Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5341 Meadow Lark Dr

Approved

Filed Nov 1, 2024 by Logan Whitcomb, Ridge Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Nov 1, 2024
Assembly type
RP
Serial number
W397655
Size
3/4
Test gauge serial
G-1282
Gauge calibration date
Feb 20, 2024
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-20-01006
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5341 Meadow Lark Dr
Owner: Cameron Hollins
Parcel 069-20-01006