← Backflow review queue
Backflow assembly test · 144 Fox Run Trl
ApprovedFiled Oct 26, 2023 by Cameron Okafor, Valley Backflow Testing · filed from phone
Report
- Date of service
- Oct 26, 2023
- Assembly type
- PVB
- Serial number
- A739285
- Size
- 3/4
- Test gauge serial
- G-7192
- Gauge calibration date
- Aug 16, 2023
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-57-01246
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
144 Fox Run Trl
Owner: Rowan Lindqvist
Parcel 059-57-01246