Backflow assembly test · 5310 Orchard Way
ApprovedFiled Aug 29, 2025 by Riley Kessler, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 29, 2025
- Assembly type
- RP
- Serial number
- K503339
- Size
- 3/4
- Test gauge serial
- G-1265
- Gauge calibration date
- Jul 9, 2025
- Check valve 1
- 6.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-10-01304
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.