← Backflow review queue
Backflow assembly test · 7319 Mill Creek Ct
ApprovedFiled Apr 12, 2026 by Riley Marsh, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Apr 12, 2026
- Assembly type
- PVB
- Serial number
- Z915477
- Size
- 3/4
- Test gauge serial
- G-9297
- Gauge calibration date
- Aug 14, 2025
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-32-01227
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7319 Mill Creek Ct
Owner: Cameron Marsh
Parcel 059-32-01227