Jefferson County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1476 Sycamore Trl

Approved

Filed Dec 8, 2025 by Cameron Calloway, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Dec 8, 2025
Assembly type
RP
Serial number
K870124
Size
1
Test gauge serial
G-5767
Gauge calibration date
May 12, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-71-01332
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1476 Sycamore Trl
Owner: Quinn Kessler
Parcel 059-71-01332