Jefferson County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 558 Laurel Way

Approved

Filed Aug 28, 2025 by Riley Marsh, Valley Backflow Testing · filed from phone

Report

Date of service
Aug 28, 2025
Assembly type
RP
Serial number
K384182
Size
3/4
Test gauge serial
G-1454
Gauge calibration date
Feb 3, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-84-01282
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

558 Laurel Way
Owner: Casey Fairley
Parcel 059-84-01282