Gilpin County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Medical Offices

Approved

Filed Oct 8, 2025 by Blake Fairley, Valley Backflow Testing · filed from phone

Report

Date of service
Oct 8, 2025
Assembly type
DC
Serial number
Z544679
Size
2
Test gauge serial
G-8223
Gauge calibration date
Feb 7, 2025
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 047-66-01059
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6261 Orchard Dr
Owner: Kessler Holdings LLC
Parcel 047-66-01059