Gilpin County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Apartments

Approved

Filed Jul 18, 2026 by Morgan Pruitt, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Jul 18, 2026
Assembly type
DC
Serial number
Z521214
Size
1 1/2
Test gauge serial
G-2438
Gauge calibration date
Apr 5, 2026
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 047-69-01195
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5723 Orchard Way
Owner: Wexler Holdings LLC
Parcel 047-69-01195