Backflow assembly test · 5762 Turkey Hill Trl
ApprovedFiled Jun 25, 2024 by Casey Ellery, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 25, 2024
- Assembly type
- RP
- Serial number
- K557214
- Size
- 3/4
- Test gauge serial
- G-4951
- Gauge calibration date
- Feb 21, 2023
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 1.6 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 047-54-01310
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.