← Backflow review queue
Backflow assembly test · 5073 Fox Run Ln
ApprovedFiled Nov 28, 2023 by Reese Vance, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 28, 2023
- Assembly type
- PVB
- Serial number
- A408501
- Size
- 3/4
- Test gauge serial
- G-4578
- Gauge calibration date
- Sep 26, 2023
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-71-01248
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
5073 Fox Run Ln
Owner: Logan Wexler
Parcel 041-71-01248