← Backflow review queue
Backflow assembly test · 3350 Orchard Way
Needs reviewFiled Nov 25, 2026 by Rowan Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Nov 25, 2026
- Assembly type
- DC
- Serial number
- K240784
- Size
- 1
- Test gauge serial
- G-5345
- Gauge calibration date
- Nov 21, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-59-01116
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
3350 Orchard Way
Owner: Avery Lindqvist
Parcel 041-59-01116