Backflow assembly test · 1529 Hickory Dr
ApprovedFiled Apr 20, 2026 by Reese Vance, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 20, 2026
- Assembly type
- RP
- Serial number
- Z808071
- Size
- 1
- Test gauge serial
- G-1794
- Gauge calibration date
- Feb 10, 2025
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-78-01305
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1529 Hickory Dr
Owner: Reese Whitcomb
Parcel 041-78-01305