El Paso County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2469 Ridgeview Way

Approved

Filed Jan 20, 2026 by Rowan Pruitt, Summit Backflow Testing · filed from phone

Report

Date of service
Jan 20, 2026
Assembly type
RP
Serial number
W171127
Size
3/4
Test gauge serial
G-7697
Gauge calibration date
Oct 27, 2025
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-10-01083
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2469 Ridgeview Way
Owner: Rowan Wexler
Parcel 041-10-01083