← Backflow review queue
Backflow assembly test · 4752 Fox Run Rd
ApprovedFiled Apr 27, 2026 by Rowan Pruitt, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Apr 27, 2026
- Assembly type
- RP
- Serial number
- Z577924
- Size
- 1
- Test gauge serial
- G-9823
- Gauge calibration date
- Jan 25, 2026
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-87-01016
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4752 Fox Run Rd
Owner: Shawn Wexler
Parcel 041-87-01016