El Paso County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Apartments

Approved

Filed Oct 1, 2024 by Rowan Ellery, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Oct 1, 2024
Assembly type
RP
Serial number
K783938
Size
1
Test gauge serial
G-2422
Gauge calibration date
Jun 16, 2024
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-15-01139
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7938 Quarry Way
Owner: Ellery Holdings LLC
Parcel 041-15-01139