← Backflow review queue
Backflow assembly test · 4450 Laurel Trl
Needs reviewFiled Nov 17, 2026 by Rowan Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Nov 17, 2026
- Assembly type
- RP
- Serial number
- A741948
- Size
- 1
- Test gauge serial
- G-3709
- Gauge calibration date
- Feb 22, 2026
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-88-01151
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
4450 Laurel Trl
Owner: Rowan Marsh
Parcel 041-88-01151