← Backflow review queue
Backflow assembly test · 2936 Laurel Dr
ApprovedFiled Oct 9, 2025 by Reese Vance, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 9, 2025
- Assembly type
- RP
- Serial number
- A979813
- Size
- 3/4
- Test gauge serial
- G-1979
- Gauge calibration date
- May 31, 2025
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-78-01330
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2936 Laurel Dr
Owner: Drew Fairley
Parcel 041-78-01330