El Paso County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2431 Meadow Lark Rd

Approved

Filed Jan 19, 2026 by Rowan Pruitt, Summit Backflow Testing · filed from phone

Report

Date of service
Jan 19, 2026
Assembly type
RP
Serial number
A441489
Size
3/4
Test gauge serial
G-4108
Gauge calibration date
Jul 13, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-82-01263
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2431 Meadow Lark Rd
Owner: Blake Lindqvist
Parcel 041-82-01263