← Backflow review queue
Backflow assembly test · 4196 Mill Creek Trl
ApprovedFiled Jul 5, 2025 by Riley Ramirez, Keystone Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jul 5, 2025
- Assembly type
- RP
- Serial number
- Z150997
- Size
- 3/4
- Test gauge serial
- G-7408
- Gauge calibration date
- Oct 30, 2024
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-30-01270
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4196 Mill Creek Trl
Owner: Morgan Stroud
Parcel 041-30-01270