Backflow assembly test · 8162 Spring Branch Ln
ApprovedFiled Jun 10, 2024 by Sam Okafor, Summit Backflow Testing · filed from phone
Report
- Date of service
- Jun 10, 2024
- Assembly type
- RP
- Serial number
- W612322
- Size
- 1
- Test gauge serial
- G-3933
- Gauge calibration date
- Mar 6, 2024
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 035-34-01289
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8162 Spring Branch Ln
Owner: Casey Hollins
Parcel 035-34-01289