← Backflow review queue
Backflow assembly test · 3517 Ridgeview Dr
Needs reviewFiled Nov 21, 2026 by Quinn Okafor, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 21, 2026
- Assembly type
- RP
- Serial number
- Z674718
- Size
- 1
- Test gauge serial
- G-9517
- Gauge calibration date
- Jun 9, 2026
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 035-69-01326
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
3517 Ridgeview Dr
Owner: Avery Wexler
Parcel 035-69-01326