Douglas County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Bakery

Approved

Filed Apr 18, 2025 by Sam Okafor, Summit Backflow Testing · filed from phone

Report

Date of service
Apr 18, 2025
Assembly type
RP
Serial number
B761091
Size
1 1/2
Test gauge serial
G-7427
Gauge calibration date
Jul 27, 2024
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-48-01340
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1273 Sycamore Ln
Owner: Danner Holdings LLC
Parcel 035-48-01340