← Backflow review queue
Backflow assembly test · 5568 Sycamore Rd
ApprovedFiled Mar 23, 2024 by Quinn Okafor, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Mar 23, 2024
- Assembly type
- PVB
- Serial number
- B227836
- Size
- 3/4
- Test gauge serial
- G-2933
- Gauge calibration date
- Sep 24, 2023
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 035-45-01012
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
5568 Sycamore Rd
Owner: Alex Ashby
Parcel 035-45-01012