Douglas County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7241 Hickory Way

Approved

Filed Aug 14, 2024 by Jamie Calloway, Ridge Backflow Testing · filed from phone

Report

Date of service
Aug 14, 2024
Assembly type
PVB
Serial number
K691683
Size
1
Test gauge serial
G-1952
Gauge calibration date
Apr 7, 2024
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-98-01294
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7241 Hickory Way
Owner: Logan Wexler
Parcel 035-98-01294