Backflow assembly test · 9811 Hickory Ct
ApprovedFiled Jul 19, 2024 by Quinn Okafor, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Jul 19, 2024
- Assembly type
- RP
- Serial number
- K411508
- Size
- 1
- Test gauge serial
- G-2055
- Gauge calibration date
- May 5, 2024
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 035-17-01058
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9811 Hickory Ct
Owner: Avery Harlow
Parcel 035-17-01058