Douglas County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6522 Orchard Ln

Approved

Filed Jun 15, 2026 by Quinn Okafor, Ridge Backflow Testing · filed from phone

Report

Date of service
Jun 15, 2026
Assembly type
DC
Serial number
K347188
Size
1
Test gauge serial
G-6315
Gauge calibration date
Apr 14, 2026
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-77-01207
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6522 Orchard Ln
Owner: Shawn Kessler
Parcel 035-77-01207