Backflow assembly test · 5074 Pine Knoll Trl

Approved

Filed Sep 9, 2026 by Sam Okafor, Summit Backflow Testing · filed from phone

Report

Date of service
Sep 9, 2026
Assembly type
RP
Serial number
B426506
Size
1
Test gauge serial
G-3893
Gauge calibration date
Oct 2, 2025
Check valve 1
0.8 psid
Check valve 1 closed tight
No
Check valve 2
3 psid
Relief valve opened at
2.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-35-01078
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.