Backflow assembly test · 2300 Spring Branch Ct

Approved

Filed Mar 15, 2025 by Jamie Calloway, Ridge Backflow Testing · filed from phone

Report

Date of service
Mar 15, 2025
Assembly type
PVB
Serial number
W892152
Size
3/4
Test gauge serial
G-9219
Gauge calibration date
Apr 6, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-80-01293
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2300 Spring Branch Ct
Owner: Blake Benton
Parcel 035-80-01293