Backflow assembly test · 2300 Spring Branch Ct
ApprovedFiled Mar 15, 2025 by Jamie Calloway, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Mar 15, 2025
- Assembly type
- PVB
- Serial number
- W892152
- Size
- 3/4
- Test gauge serial
- G-9219
- Gauge calibration date
- Apr 6, 2024
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 035-80-01293
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2300 Spring Branch Ct
Owner: Blake Benton
Parcel 035-80-01293