Denver County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Car Wash

Approved

Filed Aug 1, 2026 by Logan Wexler, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Aug 1, 2026
Assembly type
RP
Serial number
A571220
Size
2
Test gauge serial
G-4481
Gauge calibration date
Dec 12, 2025
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 031-16-01051
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7630 Laurel Trl
Owner: Ramirez Holdings LLC
Parcel 031-16-01051