Denver County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7579 Meadow Lark Rd

Approved

Filed Aug 4, 2026 by Rowan Nguyen, Keystone Plumbing & Backflow · filed from phone

Report

Date of service
Aug 4, 2026
Assembly type
RP
Serial number
W328330
Size
1
Test gauge serial
G-2903
Gauge calibration date
Jan 8, 2026
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 031-69-01330
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7579 Meadow Lark Rd
Owner: Casey Stroud
Parcel 031-69-01330