Backflow assembly test · Station Animal Hospital
ApprovedFiled Dec 28, 2024 by Logan Wexler, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 28, 2024
- Assembly type
- RP
- Serial number
- W871836
- Size
- 1
- Test gauge serial
- G-5307
- Gauge calibration date
- May 7, 2024
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 031-95-01353
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.