← Backflow review queue
Backflow assembly test · 8620 Sycamore Ct
ApprovedFiled Sep 23, 2024 by Riley Benton, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 23, 2024
- Assembly type
- PVB
- Serial number
- Z246701
- Size
- 1
- Test gauge serial
- G-3876
- Gauge calibration date
- Jun 26, 2024
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 031-77-01217
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8620 Sycamore Ct
Owner: Reese Hollins
Parcel 031-77-01217