← Backflow review queue
Backflow assembly test · 9673 Turkey Hill Trl
ApprovedFiled Dec 11, 2025 by Riley Benton, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 11, 2025
- Assembly type
- PVB
- Serial number
- W323343
- Size
- 3/4
- Test gauge serial
- G-9842
- Gauge calibration date
- Jun 10, 2025
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 031-82-01045
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
9673 Turkey Hill Trl
Owner: Hayden Hollins
Parcel 031-82-01045