Denver County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Bakery

Approved

Filed Jul 29, 2026 by Riley Benton, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Jul 29, 2026
Assembly type
RP
Serial number
W758460
Size
1 1/2
Test gauge serial
G-9128
Gauge calibration date
Nov 21, 2025
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 031-57-01177
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

768 Ridgeview Trl
Owner: Nguyen Holdings LLC
Parcel 031-57-01177