Date of service
Jun 20, 2026
Assembly type
RP
Serial number
Z760659
Size
4
Test gauge serial
G-8914
Gauge calibration date
Apr 8, 2026
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-49-01285
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.