Backflow assembly test · 2127 Meadow Lark Ct

Approved

Filed Sep 20, 2026 by Shawn Hollins, Summit Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Sep 20, 2026
Assembly type
RP
Serial number
B770009
Size
3/4
Test gauge serial
G-2054
Gauge calibration date
Dec 26, 2025
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
1.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-11-01028
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.