Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Market

Approved

Filed Jun 15, 2024 by Jamie Ramirez, Patriot Backflow Testing · filed from phone

Report

Date of service
Jun 15, 2024
Assembly type
RP
Serial number
W192054
Size
4
Test gauge serial
G-9625
Gauge calibration date
Jan 7, 2024
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-67-01293
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

3736 Ridgeview Ln
Owner: Okafor Holdings LLC
Parcel 014-67-01293