← Backflow review queue
Backflow assembly test · 732 Orchard Rd
ApprovedFiled Apr 15, 2023 by Reese Stroud, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Apr 15, 2023
- Assembly type
- DC
- Serial number
- Z713752
- Size
- 1
- Test gauge serial
- G-7184
- Gauge calibration date
- Oct 13, 2022
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-90-01089
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
732 Orchard Rd
Owner: Sam Kessler
Parcel 014-90-01089