Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Medical Offices

Approved

Filed Jun 5, 2026 by Reese Stroud, Evergreen Backflow Testing · filed from phone

Report

Date of service
Jun 5, 2026
Assembly type
DC
Serial number
W463132
Size
1
Test gauge serial
G-9981
Gauge calibration date
Feb 1, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-56-01177
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8676 Quarry Dr
Owner: Marsh Holdings LLC
Parcel 014-56-01177