Backflow assembly test · Main Street Dental

Approved

Filed Apr 21, 2024 by Reese Stroud, Evergreen Backflow Testing · filed from phone

Report

Date of service
Apr 21, 2024
Assembly type
RP
Serial number
B319364
Size
2
Test gauge serial
G-2430
Gauge calibration date
Aug 7, 2023
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-74-01132
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.