← Backflow review queue
Backflow assembly test · 2998 Pine Knoll Ct
ApprovedFiled Aug 14, 2025 by Reese Stroud, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Aug 14, 2025
- Assembly type
- RP
- Serial number
- Z181432
- Size
- 1
- Test gauge serial
- G-4517
- Gauge calibration date
- Dec 24, 2024
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-75-01121
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2998 Pine Knoll Ct
Owner: Drew Kessler
Parcel 014-75-01121