Backflow assembly test · 3888 Stone Gate Dr
ApprovedFiled Jul 16, 2023 by Jamie Ramirez, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Jul 16, 2023
- Assembly type
- RP
- Serial number
- W399531
- Size
- 1
- Test gauge serial
- G-3537
- Gauge calibration date
- Oct 8, 2022
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-14-01063
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.