Backflow assembly test · 8315 Meadow Lark Way

Approved

Filed Oct 3, 2025 by Reese Stroud, Evergreen Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Oct 3, 2025
Assembly type
RP
Serial number
B331344
Size
3/4
Test gauge serial
G-2566
Gauge calibration date
May 16, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-41-01234
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8315 Meadow Lark Way
Owner: Avery Nguyen
Parcel 014-41-01234