Backflow assembly test · 6977 Fox Run Way

Approved

Filed Nov 16, 2025 by Reese Stroud, Evergreen Backflow Testing · filed from phone

Report

Date of service
Nov 16, 2025
Assembly type
RP
Serial number
Z851252
Size
3/4
Test gauge serial
G-3246
Gauge calibration date
Aug 3, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-49-01260
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6977 Fox Run Way
Owner: Jamie Ellery